MFR 012 / MFR 012-2 Humidity Regulating
MFR 012 Electromachanical Hygrostat
Advantage:
* Adjustable relative humidity
* Easily accessible terminals
* Change-over contact
* Clip Fixing
* High switching capacity
The electromechanical hygrostat MRF 012 is designed to control enclosure heaters so that the dew point is raised when a critical relative humidity of 65% is exceeded. In this way condensation and corrosion is effectively prevented.
Switch difference*
4% RH (±3% tolerance)
Relative humidity range
35% -95%
Allow wind speed
15m/sec
Contact type
change-over contact
Contact resistance
< 10 m Ohm
Service life
>50,000 cycles
Min. switching capacity
20V AC/DC 100 mA
Max. switching capacity
25 VAC, 5 A
Connection
3-pole terminal for 2.5mm², clamping torque 0.5Nm max.: rigid wire 2.5mm², stranded wire (with wire end ferrule) 1.5mm²
Mounting
clip for 35mm DIN rail
Casing
plastic according to UL94 V-0, light grey
Dimensions/ weight
67 x 50 x 38mm
Weight
approx. 60g
Fitting position
Variable
Operating/Storage Temperature
0 to +60°C (+32 to +140°F) / -20 to +80°C (-4 to +176°F)
Protection Level
IP20