Top brand Construction
Machinery supplier
Guess you like the video
Condenser C3 Series
0
Feature

Air discharge direction

Performance ranges

Cooling capacity: from 50 to 62 kw
Air volume: from 20950 to 238230 m3/h
Sound pressure level: from 64 to 73 dB A(10m)
Air cooled condensers:customized on demand

High efficiency heat exchanger

Capacity designs for maximizing the heat transfer relative to the energy consumption of the fan.
Tube and tube coupling design for low pressure drop in the coil on the media sides(maximum 100KPa at water designing condition).
Our thermodynamic and aerodynamic designing software is long year tested and proved in Germany

Fan

Only choose low specific energy consumption fans.
Fan nozzle designs for maximum air flow and air throw.
Our fans from the world`s leading manufacturer are practically proved to be reliable in operation and long lasting.
Motor: protection class IP 54 and insulation class F.
Voltage:400V/3N/50Hz
Air separator for each fan.

Testing

Heat exchangers are supplied clean and tested at a pressure of 30 bars

Options

Coil design refrigerant: R414A, R407C.
Multiple circuits.
Sub-cooling circuits.
Stainless steel or aluminum casing.
Coated aluminum or copper fins and anti-corrosion expoxy fin.
Explosion ploof motor.
Customized fin spacing.


Technical parameter

Type

C3-062-1X800

C3-073-1X800

C3-086-1X800

C3-122-2X800

C3-145-2X800

C3-170-2X800

C3-189-3X800

C3-223-3X800

Capacity

R404A

KW

61.71

73.09

85.67

122.12

144.67

169.99

189.27

222.75

R22

60.98

71.65

82.73

117.94

139.49

162.98

177.56

208.60

R404A

Y

KW

53.45

62.23

71.02

105.90

123.28

141.00

162.91

188.55

R22

Y

52.54

60.61

68.08

102.44

118.87

134.87

152.95

176.59

Air flow

M3/h

20950

19853

18003

41902

39700

36009

62848

59557

Y

16004

15179

13829

32008

30359

27660

48009

45535

Fan Motor
3 phase/400V/50Hz

W

1800

1800

1800

3600

3600

3600

5400

5400

Y

1150

1150

1150

2300

2300

2300

3450

3450

A

3.8

3.8

3.8

7.6

7.6

7.6

11.4

11.4

Y

2.2

2.2

2.2

4.4

4.4

4.4

6.6

6.6

Sound pressure level

dB(A)

50.0

50.0

50.0

51.0

51.0

51.0

53.0

53.0

Y

10m

45.0

45.0

45.0

46.0

46.0

46.0

48.0

48.0

Dimension

L

mm

2000

2000

2000

3800

3800

3800

5600

5600

W

mm

1084

1084

1084

1084

1084

1084

1084

1084

H

mm

1328

1328

1328

1328

1328

1328

1328

1328

A

mm

1728

1728

1728

3528

3528

3528

5328

5328

B1

mm

--

--

--

1764

1764

1764

1776

1776

B2

mm

--

--

--

1764

1764

1764

1776

1776

B3

mm

--

--

--

--

--

--

1776

1776

B4

mm

--

--

--

--

--

--

--

--

X

mm

997

997

997

997

997

997

997

997

Inlet φ

mm

28.58

28.58

34.92

34.92

41.28

41.28

41.28

53.98

Inlet φ

mm

22.22

22.22

28.58

28.58

28.58

28.58

28.58

34.92

Product weight(empty)

kg

225

233

241

357

373

392

496

528



Application
Process engineering, heat / power plant, power generation, chemical industry, air conditioning chiller, heat transformer, smelting, etc.. It is suitable for all equipment which needs heat dissipation and is installed in the open air.