WHI 7 series
● Comply with the most common standard in terms of GB755, EN ISO 12100, EN 12601, EN 60204-1
● Single or double bearings are available, options for all kinds of adaptors and coupling disc
● 12-end reconnectable winding terminals to get different voltages
● Standard “H” insulation class
● Convenient installation and maintenance for rotated diodes and adaptor connected bolts
● Standard sealed maintenance-free bearings
Options
● Air filter
● Droop CT
● PMG excitation system
● Winding RTD and bearing RTD
● IP23 or IP22 Protection
● Anti-condensation heater
● Winding protection thermistor and relay
● Double bearing transition joint
WATTEK ALTERNATOR
SPECIFICATION
|
|
4 POLES |
4 POLES |
|||||
VOLTAGE |
50Hz 1500rpm |
60Hz 1800rpm |
||||||
STAR-SERIES |
380 |
400 |
415 |
416 |
440 |
480 |
||
STAR-PARALLEL |
190 |
200 |
208 |
208 |
220 |
240 |
||
TRIANGLE-SERIES |
220 |
230 |
240 |
240 |
254 |
277 |
||
WHI 7B |
RATED CAPACITY (kVA) |
1400 |
1460 |
1500 |
1690 |
1760 |
1810 |
|
|
RATED POWER (kW) |
1120 |
1168 |
1200 |
1352 |
1408 |
1448 |
|
|
EFFICIENCY (%) |
95.3 |
95.2 |
95.1 |
95.5 |
95.4 |
95.3 |
|
|
|
|
|
|
|
|
|
|
WHI 7C |
RATED CAPACITY (kVA) |
1550 |
1615 |
1660 |
1890 |
1970 |
2025 |
|
|
RATED POWER (kW) |
1240 |
1292 |
1328 |
1512 |
1576 |
1620 |
|
|
EFFICIENCY (%) |
95.7 |
95.6 |
95.5 |
95.9 |
95.8 |
95.6 |
|
|
|
|
|
|
|
|
|
|
WHI 7D |
RATED CAPACITY (kVA) |
1650 |
1720 |
1770 |
2015 |
2100 |
2160 |
|
|
RATED POWER (kW) |
1320 |
1376 |
1416 |
1612 |
1680 |
1728 |
|
|
EFFICIENCY (%) |
96.3 |
96.2 |
96.0 |
96.3 |
96.2 |
96.1 |
|
|
|
|
|
|
|
|
|
|
WHI 7E |
RATED CAPACITY (kVA) |
1900 |
1980 |
2035 |
2300 |
2395 |
2465 |
|
|
RATED POWER (kW) |
1520 |
1584 |
1628 |
1840 |
1916 |
1972 |
|
|
EFFICIENCY (%) |
96.5 |
96.1 |
96.1 |
96.3 |
96.3 |
96.2 |
|
|
|
|
|
|
|
|
|
|
WHI 7F |
RATED CAPACITY (kVA) |
2080 |
2170 |
2250 |
2600 |
2705 |
2785 |
|
|
RATED POWER (kW) |
1664 |
1736 |
1800 |
2080 |
2164 |
2228 |
|
|
EFFICIENCY (%) |
96.4 |
96.3 |
96.2 |
96.5 |
96.4 |
96.3 |
|
|
|
|
|
|
|
|
|
|
WHI 7G |
RATED CAPACITY (kVA) |
2200 |
2295 |
2360 |
2750 |
2860 |
2945 |
|
|
RATED POWER (kW) |
1760 |
1836 |
1888 |
2200 |
2288 |
2356 |
|
|
EFFICIENCY (%) |
96.0 |
95.9 |
95.9 |
96.1 |
96.0 |
95.9 |
The alternator has been designed for use in a maximum ambient temperature of 40℃ and altitude less than 1000 meters above sea level. The power factor is 0.8, and the level of raising temperature is H class (125℃)