Top brand Construction
Machinery supplier
Guess you like the video
Air-cooled Screw Chiller(7℃)
41
Feature
Products Features
1. Twin screw compressor brand is employed, with high efficiency, low noise level, less wearing and long operation time.
2.Four stage volume control or 0%-100% automatic regulation.
3.Use PLC microcomputer control from Germany SIEMENS. LCD touch screen, both English and Chinese human-machina intertace.
4.Perfect breakdown protection: high and low pressure protection, air discharge protection, oil level protection, water flow protection, reverse and lack phase protection, chilled water anti-freezing protection, cooling water overheat protection.

Product options
1.Salt water evaporator
2.Stepless energy regulation
3.Whole heat recovery/partial heat recovery
4.Pump control
5.Special power supply
6.Remote communication connector

Product specfication
Refrigerant: R22/R407C
Evaporator max water pressure drop: 1.0Mpa
Evaporator: fouling factor 0.018m2.℃/KW
Power supply: 380V/3P/50Hz
Allowable voltage fluctuate: ±5%
Allowable frequency fluctuate: ±2%
The unit uses high efficiency heat exchanger with advanced, unique shape design and systems. Units can be installed directly on the roof, or other well-ventilated place outdoors, without a separate room, space saving construction. Compact shape, appearance, unit uses “W” type coil design, space utilization, small unit size, in order to adapt to the outdoor weather conditions to ensure that the unit has a good operating results during the life cycle.
Friendy choose to use environmentally R407C, R134A or R410A refrigerant ect.
There may be change of the dimensions without pre notice. For accurate you are welcome to ask us for installing drawing.

Technical parameter

Air cooled screw(heat) chiller(single compressor) technical parameter

VA-

Type

85S

115S

150S

160S

200S

220S

255S

270S

300S

320S

Nominal cooling capacity

kw

85.0

115.0

150.0

160.0

200.0

220.0

255.0

270.0

300.0

320.0

104 kcal/h

7.3

9.9

12.9

13.8

17.2

18.9

21.9

23.2

25.8

27.5

Nominal heating capacity

kw

92.0

135.0

170.0

185.0

230.0

250.0

290.0

300.0

330.0

360.0

104 kcal/h

8.2

11.6

14.6

15.9

19.8

21.5

24.9

25.8

28.4

31.0

Operating control method

Use PLC microcomputer control

Power Supply

380V/3N/50HZ

Startup type

Y-△

Machine power

kw

30.8

40.9

50.3

59.6

70.6

76.7

85.0

88.5

99.8

108.4

Machine operating current

A

58.5

77.7

95.5

113.2

134.1

145.7

161.4

168.1

189.5

206.0

Compressor

Type

Semi-closed 5:6 asymmetric twin-screw compressor

Cooling power(kw)

27.5

36.5

45.5

50.0

61.0

66.5

75.0

78.5

86.5

94.5

Cooling current(A)

46.5

61.0

77.0

84.5

103.0

112.0

126.0

132.5

146.0

159.0

Heating power(kw)

26.5

35.0

43.5

48.0

58.5

63.5

72.0

75.5

83.0

91.0

Heating current(A)

44.5

58.5

74.0

81.0

98.5

107.0

120.0

127.0

140.0

152.0

Energy regulation

0-33%-66%-100%

0-25%-50%-75%-100%

Evaporator

Type

High efficiency dry type shell and tube heat exchanger

Flow(L/min)

14.6

19.8

25.8

27.5

34.4

37.8

43.8

46.4

51.5

55.0

Water pressure drop(kPa)

45.0

45.0

45.0

48.0

48.0

48.0

50.0

50.0

50.0

50.0

Interface size

DN65

DN80

DN100

Condenser

Type

High efficiency fin type heat exchanger

Fan quantity

6

8

8

6

6

6

6

6

8

8

Stand-alone power

0.6

0.6

0.6

1.6

1.6

1.7

1.7

1.7

1.7

1.7

Refrigerant

Type

R22

Refrigerant volume(kg)

17.0

23.0

30.0

32.0

40.0

45.0

52.0

55.0

60.0

65.0

Overall dimensions

Length(mm)

2500

2950

2950

3200

3500

3500

3700

3700

4000

4000

Width(mm)

1400

1400

1400

2200

2200

2200

2200

2200

2200

2200

Height(mm)

1925

2100

2250

2150

2150

2200

2250

2350

2150

2250

Weight

Machine weight(kg)

1900

2000

2200

2600

2850

3000

3200

3500

3800

3950

Operating weight(kG)

2200

2300

2500

2900

3150

3300

3500

3800

4100

4250

Cooling condition: Chilled water inlet/outlet temperature 12/7 ℃, ambient dry bulb temperature 35℃
Heating condition:Hot water outlet temperature 45℃, ambient dry bulb temperature 7℃, ambient wet bulb temperature 6℃

VA-

Type

350S

420S

445S

490S

525S

545S

635S

700S

745S

840S

Nominal cooling capacity

kw

350.0

420.0

445.0

490.0

525.0

545.0

635.0

700.0

745.0

840.0

104 kcal/h

30.1

36.1

38.1

42.1

45.2

46.9

54.6

60.2

64.1

72.2

Nominal heating capacity

kw

400.0

470.0

500.0

550.0

590.0

610.0

710.0

780.0

830.0

940.0

104 kcal/h

34.4

40.4

43.0

47.3

50.7

52.5

61.1

67.1

71.4

80.8

Operating control method

Use PLC microcomputer control

Power Supply

380V/3N/50HZ

Startup type

Y-△

Machine power

kw

118.5

139.0

146.0

158.0

168.5

175.5

201.0

223.5

239.5

265.0

Machine operating current

A

212.0

248.5

261.0

282.5

301.0

314.0

359.0

400.0

428.0

473.0

Compressor

Type

Semi-closed 5:6 asymmetric twin-screw compressor

Cooling power(kw)

105.0

122.0

129.0

140.0

150.5

155.0

179.0

198.5

211.0

237.0

Cooling current(A)

177.0

205.5

217.0

235.0

253.0

261.0

301.0

334.0

354.0

398.5

Heating power(kw)

101.0

117.0

123.5

134.0

144.0

148.5

171.5

190.0

202.0

227.0

Heating current(A)

170.0

197.0

208.0

225.0

242.5

250.0

288.0

320.0

334.0

382.0

Energy regulation

0-25%-50%-75%-100%

Evaporator

Type

High efficiency dry type shell and tube heat exchanger

Flow(L/min)

60.1

72.2

76.5

84.2

90.2

93.6

109.1

120.3

128.0

144.3

Water pressure drop(kPa)

52.0

55.0

55.0

58.0

60.0

60.0

62.0

70.0

75.0

80.0

Interface size

DN125

DN150

Condenser

Type

High efficiency fin type heat exchanger

Fan quantity

8

10

10

10

10

12

12

12

16

16

Stand-alone power

1.7

1.7

1.7

1.8

1.8

1.7

1.8

1.8

1.8

1.8

Refrigerant

Type

R22

Refrigerant volume(kg)

70.0

85.0

90.0

100.0

105.0

110.0

130.0

140.0

150.0

170.0

Overall dimensions

Length(mm)

4200

4500

5000

5800

5800

6000

6200

6500

8000

8000

Width(mm)

2200

2200

2200

2200

2200

2200

2200

2200

2200

2200

Height(mm)

2250

2300

2350

2350

2350

2350

2450

2450

2350

2450

Weight

Machine weight(kg)

4350

4550

4850

5300

5500

5800

6250

6550

7350

7500

Operating weight(kG)

4650

4850

5150

5600

5800

6100

6550

6850

7650

7800

Cooling condition: Chilled water inlet/outlet temperature 12/7 ℃, ambient dry bulb temperature 35℃
Heating condition:Hot  water outlet temperature 45℃, ambient dry bulb temperature 7℃, ambient wet bulb temperature 6℃

Air cooled screw(heat) chiller(double compressor) technical parameter


VA-

Type

170D

230D

300D

320D

400D

440D

510D

540D

600D

640D

Nominal cooling capacity

kw

170.0

230.0

300.0

320.0

400.0

440.0

510.0

540.0

600.0

640.0

104 kcal/h

14.6

19.8

25.8

27.5

34.4

37.8

43.9

46.4

51.6

55.0

Nominal heating capacity

kw

190.0

270.0

340.0

370.0

460.0

500.0

580.0

600.0

660.0

720.0

104 kcal/h

16.3

23.2

29.2

31.8

39.6

43.0

49.9

51.6

56.8

61.9

Operating control method

Use PLC microcomputer control

Power Supply

380V/3N/50HZ

Startup type

Y-△

Machine power

kw

61.6

81.8

100.6

119.2

141.2

153.4

170.0

177.0

199.6

216.8

Machine operating current

A

117.0

155.4

191.0

226.4

268.2

291.4

322.8

336.2

379.0

412.0

Compressor

Type

Semi-closed 5:6 asymmetric twin-screw compressor

Cooling power(kw)

55.0

73.0

91.0

100.0

122.0

133.0

150.0

157.0

173.0

189.0

Cooling current(A)

93.0

122.0

154.0

169.0

206.0

224.0

252.0

265.0

292.0

318.0

Heating power(kw)

53.0

70.0

87.0

96.0

117.0

127.0

144.0

151.0

166.0

182.0

Heating current(A)

89.0

117.0

148.0

162.0

197.0

214.0

240.0

254.0

280.0

304.0

Energy regulation

0-16.5%-33%-...100%                         0-12.5%-25%-37.5%-....100%

Evaporator

Type

High efficiency dry type shell and tube heat exchanger

Flow(L/min)

29.2

39.5

51.5

55.0

68.7

75.6

87.6

92.8

103.1

110.0

Water pressure drop(kPa)

47.0

47.0

50.0

50.5

55.0

55.0

55.0

58.0

58.0

58.0

Interface size

DN80

DN100

DN125

DN150

Condenser

Type

High efficiency fin type heat exchanger

Fan quantity

6

6

8

8

10

10

10

12

12

12

Stand-alone power

1.2

1.2

1.2

1.2

1.7

1.7

1.7

1.7

1.8

1.8

Refrigerant

Type

R22

Refrigerant volume(kg)

34.0

46.0

60.0

64.0

80.0

90.0

104.0

110.0

120.0

130.0

Overall dimensions

Length(mm)

3500

3500

4000

4000

4500

5000

5800

6000

6200

6200

Width(mm)

2150

2200

2200

2200

2200

2200

2200

2200

2200

2200

Height(mm)

2200

2200

2150

2250

2300

2350

2350

2350

2450

2550

Weight

Machine weight(kg)

2800

3000

3900

4250

4650

4950

5600

5950

6250

6450

Operating weight(kG)

3100

3300

4200

4550

4950

5250

5900

6250

6550

6750

Cooling condition: Chilled water inlet/outlet temperature 12/7 ℃, ambient dry bulb temperature 35℃
Heating condition:Hot water outlet temperature 45℃, ambient dry bulb temperature 7℃, ambient wet bulb temperature 6℃

Application
Chemical, chemical fiber, plastic, oil, food, pharmaceutical, military, printing, painting, electroplating, electronics and other industries
Service
Pre-sale services

1. Professional and technical consultation and communication.

2. Equipment selection and quotation.

3. Product application solutions recommendations.

4. Engineering solutions.


After-sale services

Warranty: 12 months guarantee for all products.

Within warranty, any problem caused by the defects of the machine itself, we will offer its service until the problem solved.

Over warranty, we will offer maintenance activity by cost only.

FAQ

Q: How to choose air cooled system or water cooled system? Air cooled is better or water cooled is better?

A: In terms of installation simplicity, the air cooled system is more convenient than the water-cooled system and does not need to connect cooling towers. The water cooled system needs to be connected to the cooling tower then it can run. In terms of energy efficiency, the water cooled system has higher energy efficiency than the air cooled system. Specifically, according to your environment and situation, engineers will design an optimization plan for you.


Q: What is the outlet temperature of your chiller?

A: -55 to 15 centigrade.


Q: What’s payment terms?

A: 50% as deposit, 50% before delivery by T/T, Western Union and Paypal is our regular payment terms. D/P, L/C need to have a discussion.


Q: What is the warranty of water chiller?

A: The standard warranty is 12 months.


Q: What is the  delivery time?

A: Usually around 30 days.


TOP
×
Login

Not a member yet? Create an account

I'am a supplier Login
×
Register

Already got an account? Login

Become a supplier Register

VA-

Type

700D

840D

890D

980D

1050D

1090D

1270D

1400D

1490D

1680D

Nominal cooling capacity

kw

700.0

840.0

890.0

980.0

1050.0

1090.0

1270.0

1400.0

1490.0

1680.0

104 kcal/h

60.2

72.2

76.5

84.3

90.3

93.7

109.2

120.4

128.1

144.5

Nominal heating capacity

kw

800.0

940.0

1000.0

1100.0

1180.0

1220.0

1420.0

1560.0

1660.0

1880.0

104 kcal/h

68.8

80.8

86.0

94.6

101.5

104.9

122.1

134.2

142.8

161.7

Operating control method

Use PLC microcomputer control

Power Supply

380V/3N/50HZ

Startup type

Y-△

Machine power

kw

237.0

278.0

292.0

316.0

337.0

351.0

402.0

447.0

479.0

530.0

Machine operating current

A

424.0

497.0

522.0

565.0

602.0

628.0

718.0

800.0

856.0

946.0

Compressor

Type

Semi-closed 5:6 asymmetric twin-screw compressor

Cooling power(kw)

210.0

244.0

258.0

280.0

301.0

310.0

358.0

397.0

422.0

474.0

Cooling current(A)

354.0

411.0

434.0

470.0

506.0

522.0

602.0

668.0

708.0

797.0

Heating power(kw)

202.0

234.0

247.0

268.0

288.0

297.0

343.0

380.0

404.0

454.0

Heating current(A)

340.0

394.0

416.0

450.0

485.0

500.0

576.0

640.0

668.0

764.0

Energy regulation

0-12.5%-25%-37.5%-....100%

Evaporator

Type

High efficiency dry type shell and tube heat exchanger

Flow(L/min)

120.3

144.3

152.9

168.4

180.4

187.3

218.2

240.5

256.0

288.7

Water pressure drop(kPa)

52.0

55.0

55.0

58.0

60.0