W-TEL high frequency power supply system is developed by decades of exploitation and on-line operation experience. To meet the demands of the network construction for 3G/4G 、FTTX 、data communication equipment 、transmission equipment and access equipment .With high reliability、high power density、high-performance、all digital insert-frame communication power system function. With battery management and power system monitor function , match with proper sensor can realize environment supervision and supply more than one standby supervise capacity , Also can support RS232 、RS485 interface for IP ,convenient for realize remote supervision and unattended.
· System Features
· Adopt up-and-down in-and-out wiring methods, all front operation, easy installation and maintenance.
· Structure flexible, indoor and outdoor type, can reach IP55.
· With AC /DC /ACDC /ACDC integrated multi-system structure, fit for multi -application
· Excellent AC/DC/ signal lightening protection
· Rectifier support normal efficiency and high efficiency mixed insertion, more environmental protection.
· Input voltage range of rectifier module is 90-300 Vac. power grid with high applicability.
· Rectifier module with nondestructive hot-swap tech, support on-line maintenance
· Excellent battery management function, effectively extend the service life of the battery.
· With RS232/RS485, interface, dry contact and multi- communication interface, flexible networking
Configuration |
W-TEL-200 |
W-TEL-400 |
W-TEL-600 |
|
System capacity |
200A |
400A |
600A |
|
Supervisory module |
SM32E |
|||
Rectifier module |
RM4850/RM4850H |
|||
AC/DC distribution unit |
support 24P AC/DC circuit breaker installation position |
|||
Dry contact |
6 ways input ,6 ways output, user-defined |
|||
Frame construction |
19inch 6U |
19inch 8U |
19inch 10U |
|
Optional configuration |
3U AC/DC distribution unit, multi-users electric power consumption inspection function, B+C SPD, AC electric power inspection, multi-level load function and TCP/IP communication. |
Configuration |
W-TEL-14 |
W-TEL-18 |
Cabinet inside size |
800W*800D*1400H |
800W*800D*1800H |
DC Power system |
IPS30000 series insert power system |
|
Distribution unit |
3U AC/3U DC distribution unit |
|
Temperature control equipment |
equipment compartment heat exchange, AC compressor air condition. battery compartment TEC. |
|
Inside space |
Equipment compartment 22U,Battery compartment 18U (2sets of 150AH battery) |
Equipment compartment 22U,Battery compartment 18U (1set of 150A H battery) |
Cabinet material |
sandwich steel panel |
|
Others |
48v light ,entrance guard ,battery guard against label ,hydrogen remove fan. |
Rectifier Module |
W-TEL-4850 |
W-TEL-4850H |
W-TEL-4830 |
W-TEL-4830H |
|
Input voltage |
90~300Vac(176V~300V full load output,90~176V decline load output) |
||||
Output voltage |
typical 53.5Vdc(range 42~58Vdc) |
||||
Output current |
0-50A |
0-30A |
|||
Power factor |
≥0.99 |
||||
Input frequency |
45~65HZ |
||||
Output frequency |
2900W |
1740W |
|||
Protection function |
input overvoltage protection ,output overvoltage protection , output over current protection ,over temperature alarm and protection |
||||
Overvoltage protection point |
59Vdc |
||||
Output current limit |
54A |
36A |
|||
Ripple (vp-p) |
≤200mv (at rated input /output state ,plus 0.1uF ceramic capacitor and 10uF high frequency electrdytic capacitor for each ,bandwidth is 20MHz measurement.) |
||||
Call constant noise |
≤2mv |
||||
Voltage stability accuracy |
≤±0.6 |
||||
Dimension |
242.1*102.7*83.8mm |
208×126×41.6mm |
|||
Startup time |
≤10S |
||||
Output power |
≥92% |
≥95% |
≥92% |
≥95% |